LCD Series
Digital Multifunction Meter
Intelligent Load Manager
Automatic Power Factor Controller
Model Number | PE 66XX | PE 66XXSS | PE 66XX-E3 | PE 66PK |
---|---|---|---|---|
Key Features | - Available in 4 to 16 stages - Intelligent KVAR based switching - LED indication of capacitor stages - Dual setting for Generator and EB power factor (Optional) - Available in HT-CT sensing -Switching delay of 1 sec |
- Intelligent KVAR based switching - Intelligent with best fit control - Ideal for thyristor modules - Ajustable capacitor time delays - Stages 4 to 16 - Menu driven user friendly handling - Alarm output - Easy to install - Smart switching |
- User Friendly interface - Easy to install. - Complete menu guided programming operation and display - Best fit capacitor switching - Test mode for Panel Testing - No of stages can be configured at site - Automatic / Manual capacitor value feed - Password protected settings. - HT CT sensing for HT application (Optional) |
- Intelligent KVAR based switching - Friendly user interface - Easy to install |
Control Features | - Password protected - Site settable a. %KVAR switching capacity b. Target PF c. CT primary d. Switching delay e. Lockout time for power ON f. Harmonic(THD) overload protection g. No.of stages can be selected - Capacitor disconnection in case of low current - Auto identification or manual feeding of capacitor values - Manual switching facility - Test mode facility |
- Password protection for settings - Adjustable %KVAR switching capacity - Adjustable value of Target PF - Adjustable CT primary - Adjustable time delay from 1 sec for switching ON insteps for 1 sec - Models available in 4,6,8,12,14,16 steps - Adjustable settings for % THD (Total harmonic distortion) protection - Disconnection in case of low current - Adjustable number of maximum stages. - Adjustable lock time for power ON - Auto identification or Manual feeding of capacitor values - Manual switching facility - Test mode facility |
- Site adjustable CT Primary. - Adjustable value of Target PF - Switching Delay - Lock out time for power on - Capacitor disconnection in case of Low Current - Auto identification or manual feeding of capacitor values - Manual switching facility - Test mode facility |
- Site settable C.T. Primary from 5 to 7500 A - Target PF - Switching delay - Lockout time for power ON - Auto identification or Manual feeding of capacitor values - Manual switching facility - Test mode facility - Password protection for settings |
Communication | - | Modbus RS485 (Optional) | - | - |
Alarm | - | - Under compensation - Over compensation - Under current - Over voltage - Excess Total harmonic distortion (THD) |
- | - |
Display | Large alphanumeric LCD Display (2 x 16 characters) | Large alphanumeric LCD display (20 X 4 characters) | ||
Voltage Input | 415V AC ± 15% | 230V AC ± 15% OR 415V AC ± 15% 110V AC (Optional) (HT Model) |
230V AC ± 15% | |
Current Input | Standard 5A (1A on request) | …./5A | Standard 5A (1A on request) | Standard 5A (1A on request) |
Auxiliary Supply | 230V AC ± 10% | |||
Frequency | 50/60 Hz | |||
Low Current | 1% (50mA) | |||
Operating Temp. | +5°C to +60°C | |||
Accuracy | Class 1.0 | Class 1.0 (Class 0.5, 0.2 Optional) | Class 1.0 | |
Switching Contact | 10A at 250V AC | - | 10A at 250V AC | |
Switching Interval | 5 to 1200 sec | 1 to 1200 sec | - | 5 to 1200 sec |
Intelligent (Best fit) | Most Intelligent (Best fit) | - | Intelligent (Best fit) | |
No.of Stages | 4,6,8,12,14,16 | 6, 8, 10. 12, 16 | Available in 12 stages | |
Target PF | - | 0.71 Lag to 0.80 Lead | - | - |
Mode | - | Auto/Manual | Auto/Manual | Auto/Manual |
Dimensions | 144(L)x144(W)x80(D) | |||
Panel Cut Out | 138mm x 138mm | |||
Weight | 1.5Kg | 1Kg | - | 1.5Kg |
Parameters | Voltage, Current, Power factor | Voltage, Current, Power factor | Phase to Neutral Voltage & Current | Power Factor (RYB) |
KVA and KVAR on display | KVA and KVAR on display | KVA and KVAR on display | Voltage (RYB) | |
Shortfall KVAR/ Excess KVAR | Shortfall KVAR/ Excess KVAR | Power Factor of each phase | Current (RYB) | |
THD - 3rd to 13th harmonics | THD - 3rd to 13th harmonics & % THD | Shortfall KVAR/ Excess KVAR with sign | Shortfall KVAR | |
Capacitor Values | Capacitor Values | KW, KVA and KVAR each phase | ||
Capacitor stages status | ||||
Alarm Message | ||||