LCD Series

Model Number PE 66XX PE 66XXSS PE 66XX-E3 PE 66PK
Key Features - Available in 4 to 16 stages
- Intelligent KVAR based switching
- LED indication of capacitor stages
- Dual setting for Generator and EB power factor (Optional)
- Available in HT-CT sensing
-Switching delay of 1 sec
- Intelligent KVAR based switching
- Intelligent with best fit control
- Ideal for thyristor modules
- Ajustable capacitor time delays
- Stages 4 to 16
- Menu driven user friendly handling
- Alarm output
- Easy to install
- Smart switching
- User Friendly interface
- Easy to install.
- Complete menu guided programming operation and display
- Best fit capacitor switching
- Test mode for Panel Testing
- No of stages can be configured at site
- Automatic / Manual capacitor value feed
- Password protected settings.
- HT CT sensing for HT application (Optional)
- Intelligent KVAR based switching
- Friendly user interface
- Easy to install
Control Features - Password protected
- Site settable
a. %KVAR switching capacity
b. Target PF
c. CT primary
d. Switching delay
e. Lockout time for power ON
f. Harmonic(THD) overload protection
g. No.of stages can be selected
- Capacitor disconnection in case of low current
- Auto identification or manual feeding of capacitor values
- Manual switching facility
- Test mode facility
- Password protection for settings
- Adjustable %KVAR switching capacity
- Adjustable value of Target PF
- Adjustable CT primary
- Adjustable time delay from 1 sec for switching ON insteps for 1 sec
- Models available in 4,6,8,12,14,16 steps
- Adjustable settings for % THD (Total harmonic distortion) protection
- Disconnection in case of low current
- Adjustable number of maximum stages.
- Adjustable lock time for power ON
- Auto identification or Manual feeding of capacitor values
- Manual switching facility
- Test mode facility
- Site adjustable CT Primary.
- Adjustable value of Target PF
- Switching Delay
- Lock out time for power on
- Capacitor disconnection in case of Low Current
- Auto identification or manual feeding of capacitor values
- Manual switching facility
- Test mode facility
- Site settable C.T. Primary from 5 to 7500 A
- Target PF
- Switching delay
- Lockout time for power ON
- Auto identification or Manual feeding of capacitor values
- Manual switching facility
- Test mode facility
- Password protection for settings
Communication - Modbus RS485 (Optional) - -
Alarm - - Under compensation
- Over compensation
- Under current
- Over voltage
- Excess Total harmonic distortion (THD)
- -
Display Large alphanumeric LCD Display (2 x 16 characters) Large alphanumeric LCD display (20 X 4 characters)
Voltage Input 415V AC ± 15% 230V AC ± 15% OR
415V AC ± 15%
110V AC (Optional) (HT Model)
230V AC ± 15%
Current Input Standard 5A (1A on request) …./5A Standard 5A (1A on request) Standard 5A (1A on request)
Auxiliary Supply 230V AC ± 10%
Frequency 50/60 Hz
Low Current 1% (50mA)
Operating Temp. +5°C to +60°C
Accuracy Class 1.0 Class 1.0 (Class 0.5, 0.2 Optional) Class 1.0
Switching Contact 10A at 250V AC - 10A at 250V AC
Switching Interval 5 to 1200 sec 1 to 1200 sec - 5 to 1200 sec
Intelligent (Best fit) Most Intelligent (Best fit) - Intelligent (Best fit)
No.of Stages 4,6,8,12,14,16 6, 8, 10. 12, 16 Available in 12 stages
Target PF - 0.71 Lag to 0.80 Lead - -
Mode - Auto/Manual Auto/Manual Auto/Manual
Dimensions 144(L)x144(W)x80(D)
Panel Cut Out 138mm x 138mm
Weight 1.5Kg 1Kg - 1.5Kg
Parameters Voltage, Current, Power factor Voltage, Current, Power factor Phase to Neutral Voltage & Current Power Factor (RYB)
KVA and KVAR on display KVA and KVAR on display KVA and KVAR on display Voltage (RYB)
Shortfall KVAR/ Excess KVAR Shortfall KVAR/ Excess KVAR Power Factor of each phase Current (RYB)
THD - 3rd to 13th harmonics THD - 3rd to 13th harmonics & % THD Shortfall KVAR/ Excess KVAR with sign Shortfall KVAR
Capacitor Values Capacitor Values KW, KVA and KVAR each phase
Capacitor stages status
Alarm Message